125A 3P - 25KA Schneider Circuit Breaker

Product Photo Product Photo 1 Product Photo 2 Product Photo 3 Product Photo 4
30% OFF

Rs. 60,385.00   Rs. 46,450.00

ADD TO CART

Model No: LV516302

Brand: Schneider

 Schneider

Call now

0774 953 653 | 0777 731 670 | 0771 200 201

Share

             

Brand  - Schneider

Model - LV516302

Range of Product - EasyPact CVS100...250

Product Name - EasyPact CVS

Device short name - CVS160B

Product or Component Type - Circuit Breaker 

Device Application - Distribution

Poles Description - 3P

Protected Poles Description - 3D

Earth leakage protection (Vigi add on) Without

[In] Rated current 125A at 40 °C

Network Type - AC

Utilisation Category - Category A

[Icu] Breaking capacity - 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

Trip unit name - TM-D
Trip unit technology - Thermal-magnetic
Trip unit rating - 125A at 40 °C
Protection type - Short-circuit protection (magnetic)
Overload protection (thermal)

Complementary
[Uimp] rated impulse withstand voltage - 8 kV conforming to EN/IEC 60947-2
Network frequency - 50/60 Hz
Breaking capacity code - B
[Ics] rated service breaking capacity - 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability - 25000 cycles
Electrical durability - 12000 cycles 415 V In conforming to IEC 60947-2
Control type - Toggle
Thermal protection adjustment range - 87.5..…125 A
Long time pick-up adjustment type Ir - Adjustable

Long time pick-up adjustment range - 0.7...1 x In
Long time delay adjustment type - Fixed
Instantaneous pick-up adjustment type Ii - Fixed
Instantaneous pick-up adjustment range - 1250 A
Contact position indicator - Yes
mounting support - Backplate
mounting mode - Fixed
Upside connection - Front
downside connection - Front
Connections - terminals Screw connection
Connection pitch - 35 mm
Compatibility code - CVS160
Width - 105 mm
Depth - 86 mm
Height - 161 mm
net weight - 1.5 kg

Environment
Standards - IEC 60947-2 /EN 60947-2
product certifications - GOST IEC
Electrical shock protection class - Class II
Pollution degree - 3 conforming to IEC 60664-1
IP degree of protection - IP40
ambient air temperature for operation -25…70 °C
ambient air temperature for storage -50…85 °C

Packing Units
Unit Type of Package 1 - PCE
Number of Units in Package 1 - 1
Package 1 Height - 13.500 cm
Package 1 Width - 11.300 cm
Package 1 Length - 19.200 cm
Package 1 Weight - 1.755kg

Unit Type of Package 2 - S04
Number of Units in Package 2 - 12
Package 2 Height - 30.000 cm
Package 2 Width - 40.000 cm
Package 2 Length - 60.000 cm
Package 2 Weight - 21.622 kg