Products
Building Material Power Tools Hand Tools Architectural Hardware Safety Products Electrical Products - Conduit Pipes - Cable Trunkings - Bends - Connector Bars - Single Core Cables - Auto Cables - Welding Cables - Telephone Cables - Fans - Two Core Cables - Coaxial Cables - Control Cables - Panel Wires (PVC Insulated Cables) - Screen Cables - LED Bulbs - LED Panel Lights - Tube Lights - Flood Lights - Residual Current Circuit Breakers - Miniature Circuit Breakers - Switch Disconnectors - Electric Isolaters - Circuit Breakers (Fixed Type) - Circuit Breakers (Adjustable Type) - Contactor - D Range - Overload Relay - D Range - LED Indicators - Push Buttons - Electric Mechanical Interlocks - Timer Switches - Power Energy Meters - Four Core Cables - Five Core Cabels - Wall Mounting Enclosures Cast Iron Products Powertool Accessories Plumbing Products PVC Products Rubber Products General Hardware Chemical Products Painting Products18A 7.5KW / 10HP 415V Schneider Contactor D Range
30% OFF
Rs. 23,764.00 Rs. 18,280.00
Model No: LC1D18N7
Brand: Schneider
Call now
0774 953 653 | 0777 731 670 | 0771 200 201
Share
Brand - Schneider
Model - LC1D18N7
Range of Product - TeSys Deca
Product or Component Type - Contactor
Device short Name - LC1D
Contactor Application - Resistive load
Motor control
Utilisation category - AC-1
AC-4
AC-3
AC-3e
Poles Description - 3P
[Ue] Rated operational voltage - Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] Rated operational current - 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] Control circuit voltage - 415 V AC 50/60 Hz
Complementary
Motor power kW - 4 kW at 220...230 V AC 50/60 Hz (AC-3)
7.5 kW at 380...400 V AC 50/60 Hz (AC-3)
9 kW at 415...440 V AC 50/60 Hz (AC-3)
10 kW at 500 V AC 50/60 Hz (AC-3)
10 kW at 660...690 V AC 50/60 Hz (AC-3)
4 kW at 400 V AC 50/60 Hz (AC-4)
4 kW at 220...230 V AC 50/60 Hz (AC-3e)
7.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
9 kW at 415...440 V AC 50/60 Hz (AC-3e)
10 kW at 500 V AC 50/60 Hz (AC-3e)
10 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor Power hp - 1 hp at 115 V AC 50/60 Hz for 1 phase motors
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
10 hp at 460/480 V AC 50/60 Hz for 3 phases motors
15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code - LC1D
Pole contact composition - 3 NO
Protective cover - With
[Ith] conventional free air thermal current - 10 A (at 60 °C) for signalling circuit
32 A (at 60 °C) for power circuit
Irms rated making capacity - 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
300 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity - 300A at 440 V for power circuit conforming to IEC 60947
[Icw] Rated short-time withstand current - 145 A 40 °C - 10 s for power circuit
240 A 40 °C - 1 s for power circuit
40 A 40 °C - 10 min for power circuit
84 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated Fuse Rating - 10 A gG for signalling circuit conforming to IEC 60947-5-1
50 A gG at <= 690 V coordination type 1 for power circuit
35 A gG at <= 690 V coordination type 2 for power circuit
Average impedance - 2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole - 2.5 W AC-1
0.8 W AC-3
0.8 W AC-3e
[Ui] rated insulation voltage - Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Overvoltage category - III
Pollution degree - 3
[Uimp] rated impulse withstand voltage - 6 kV conforming to IEC 60947
Safety reliability level - B10d 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1
Mechanical durability - 15 Mcycles
Electrical durability - 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
1 Mcycles 32 A AC-1 at Ue <= 440 V
1.65 Mcycles 18 A AC-3e at Ue <= 440 V
Control circuit type - AC at 50/60 Hz standard
Coil technology - Without built-in suppressor module
Control circuit voltage limits - 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush Power in VA - 70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA - 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation - 2…3 W at 50/60 Hz
Operating time - 12...22 ms closing
4...19 ms opening
Maximum operating rate - 3600 cyc/h 60 °C
Maximum operating rate - 3600 cyc/h at 60 °C
Permissible ambient air temperature around the device - 40…60 °C
60…70 °C with derating
Operating altitude - 0...3000 m
Fire resistance - 850 °C conforming to IEC 60695-2-1
Flame retardance - V1 conforming to UL 94
Mechanical robustness - Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor open (10 Gn for 11 ms)
Shocks contactor closed (15 Gn for 11 ms)
Height - 77 mm
Width - 45 mm
Depth - 86 mm
Net weight - 0.33 kg
Packing Units
Unit Type of Package 1 - PCE
Number of Units in Package 1 - 1
Package 1 Height - 5.000 cm
Package 1 Width - 9.200 cm
Package 1 Length - 11.200 cm
Package 1 Weight - 359.000 g
Unit Type of Package 2 - S02
Number of Units in Package 2 - 20
Package 2 Height - 15.000 cm
Package 2 Width - 30.000 cm
Package 2 Length - 40.000 cm
Package 2 Weight - 7.524 kg
18 Months Company Warranty